The Results tab stores testing information, such as the type of test, when it was performed, and measurements taken during the test. It also contains a grid that stores information about the flowed hydrants and their measurements.
Field Name |
Special Function |
Test Time |
The Test Time field is automatically populated with the total testing time (in minutes). This is based on: Test Time = Start Time - End Time |
Test Static (psi) |
This field stores the pressure reading of the residual hydrant before the test began. Note: The data in this field is used to find the Half Static Press value and calculate the Flow at 20 psi. |
Residual (psi) |
This field stores the pressure reading during the testing. Note: The data in this field is used to calculate the Flow at 20 psi and the Flow at Half. |
Discharge (gpm)
|
This sums all the values in the Discharge of Q fields in the Flow Hydrants grid. Note: Click in the field and press F5 to calculate. This function is only effective if the test occurred on multiple flowed hydrants. |
Volume (gal)
|
This field stores the total amount (in gallons) of water displaced during the test. This is based on the data in the Volume Released field in each flowed hydrant result record. Note: Click in the field and press F5 to calculate. This function can be used regardless of how many flow hydrants were tested. |
Turn Off Valume Calc |
Check this box to stop the Volume field from auto-calculating. |
Half Static Press |
This field is disabled if the Test Static (psi) field value is greater than or equal to 40. If the Test Static (psi) field value is less than 40, then this field is auto-populated with half the value of the Test Static (psi) field. |
Flow at 20 psi |
This field is auto-calculated based on the Discharge, Test Static, and Residual fields. Flow at 20psi = {(Flow Factor* x Discharge) x [((Pressure Factor* x Test Static) - Min Fire Flow Press*) / (Pressure Factor* x (Test Static - Residual))]}^.54 * These values are based on SAE Factors by default. They can be updated using the Set Factors Toolkit function. Defaults: Flow Factor = 1, Pressure Factor = 1, Min Fire Flow Press = 20 |
Flow at Half |
This field is auto-calculated based on the Discharge, Half Static Press, and Residual fields. Flow at Half = {(Flow Factor* x Discharge) x [((Pressure Factor* x Half Static Press) - Min Fire Flow Press*) / (Pressure Factor* (Half Static Press - Residual))]^.54 * These values are based on SAE Factors by default. They can be updated using the Set Factors Toolkit function. Defaults: Flow Factor = 1, Pressure Factor = 1, Min Fire Flow Press = 20 |
Flow Hydrant Grid
This grid stores information about each hydrant that is allowed to flow during the flow test and helps determine the total volume released from each of the flowed hydrants.
A sample of the grid appears below. Sort records in the grid by clicking on the headings. An up or down arrow (highlighted in orange below) will appear signifying ascending or descending order.